Description
GD-70D SGU Sensor
SGU Gas Detected | Detection Range | Alarm 1 | Alarm 2 | Increments | Part # |
---|---|---|---|---|---|
COS (Carbonyl sulfide) | 0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MCOS |
C2H2Cl2 (Dichloroethylene) | 0 - 600 ppm | 200 ppm | 400 ppm | 5 ppm | GD-70D-MDCE |
CH2Cl2 (Dichloromethane) | 0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MDCM |
R32 (Difluoromethane) | 0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MR32 |
R41 (Fluoromethane) | 0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MR41 |
H2 (Hydrogen) | 0 - 500 ppm | 200 ppm | 400 ppm | 5 ppm | GD-70D-MH2-S500 |
0 - 1,000 ppm | 250 ppm | 500 ppm | 10 ppm | GD-70D-MH2-S1K | |
0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MH2-S2K | |
0 -2.00% volume (SGU Type) | 0.50% vol | 1.00% vol | 0.01% vol | GD-70D-MH2-20K | |
IPA (Isopropyl alcohol) | 0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MIPA-2K |
Methane | 0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MCH4-2K |
0 - 5,000 ppm | 2,000 ppm | 4,000 ppm | 25 ppm | GD-70D-MCH4-5K | |
0 - 2% volume (SGU Type) | 0.50% vol | 1.00% vol | 0.01% vol | GD-70D-MCH4-20K | |
CH3OH (Methanol) | 0 - 1,000 ppm | 250 ppm | 500 ppm | 10 ppm | GD-70D-MCH3OH-1 |
0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MCH3OH-2 | |
C3H8 (Propane) | 0 - 2,000 ppm | 500 ppm | 1,000 ppm | 10 ppm | GD-70D-MC3H8-2K |
0 - 5,000 ppm | 2,000 ppm | 4,000 ppm | 10 ppm | GD-70D-MC3H8-5K |
ESU | ESU + PLU *1 | SSU + PLU *1 | NCU | SGU | |
---|---|---|---|---|---|
Detection principle | Electrochemical type | Pyrolysis-particle type | New ceramic (Catalytic combustion) | Semiconductor | |
Gas to be detected | Refer to list of detectable gases | NF3/COS | 0-15ppm TEOS in air and others | Combustible gas | Combustible gas |
Toxic gas | |||||
Detection range | See Detection Gas chart | ||||
Detection method | Pump suction type | Pump suction type/pyrolysis type | Pump suction type | ||
Alarm setpoint value | See Detection Gas chart | ||||
Alarm accuracy | Within ±30% to the alarm setpoint value | ±25% to the alarm setpoint value | Combustible: ±25% to the alarm setpoint value | ||
Toxic: ±30% to the alarm setpoint value | |||||
Alarm delay time | 60 seconds or less by providing the gas 1.6 times the alarm setpoint (excluding delay in the tube and in the communication) | 30 seconds or less by providing the gas 1.6 times the alarm setpoint (excluding delay in the tube and in the communication) | Combustible: 30 seconds or less by providing the gas 1.6 times the alarm setpoint (excluding delay in the tube and in the communication) | ||
Toxic: 60 seconds or less by providing the gas 1.6 times the alarm setpoint (excluding delay in the tube and in the communication) | |||||
Alarm type | Two-step alarm (H-HH) | ||||
Power consumption | Approx. 1.5 W (Max. 4 W) | Approx. 3W (Max. 5.5W) | Approx. 2.5W (Max. 5W) | ||
Power consumption (EA) | 24 V: Approx. 3W (Max. approx. 5W) | 24 V: Approx. 4.5W (Max. approx. 6.5W) | 24 V: Approx. 4W (Max. approx. 6W) | ||
PoE: Approx. 4.5W (Max. approx. 7W) | PoE: Approx. 5.5W (Max. approx. 8.5W) | PoE: Approx. 5.5W (Max. approx. 7W) | |||
Power consumption (DV) | Approx. 2 W (Max. 4.5 W) | Approx. 3.5W (Max. 6W) | Approx. 3W (Max. 5.5W) | ||
Operating temperature (at a constant condition) | 0 - 40ºC | 0 - 40ºC | 0 - 40ºC | 0 - 40ºC | 0 - 40ºC |
Operating humidities (Non-condensing) | 30 - 70%RH | 30 - 80%RH | 95%RH or less | ||
Self diagnosis function | Sensor trouble, system failure | ||||
Date logging function | Event history, alarm history, calibration history, Alarm trend (60 sec. before/after 1st alarm) |