Smart Transmitter, GD-70D toxic gas monitor, Silane, 0-15 ppm with ESU-23AH sensor

$1,595.00

Description

GD-70D for Silane, 0-15 ppm (ESU-23AH)

The new Model GD-70D smart gas detection transmitter series sets a new standard for performance, flexibility, and versatility. The GD-70D sample-draw transmitter offers an array of sensor technologies unmatched in the industry, including unique offerings, such as our hydrogen-specific or LEL versions.

The long life high capacity pump and wide variety of sensing elements are replaceable in a few seconds, with no tools required! The smart sensors retain all calibration and sensor-specific data in non-volatile memory, so sensors can be hot-swapped in the field with no programming required. The sensors also retain calibration information, which means they can be conveniently calibrated separate from the transmitter, avoiding transport of calibration gases to the field location. The GD-70D firmware automatically corrects for long-term zero and span “drift” minimizing maintenance and maximizing reliability.

The GD-70D can be used as a stand-alone device, offering a number of communication protocols to existing PLC systems, or can be integrated with RKI’s Beacon series of single and multi-channel controllers.

All GD-70D transmitters include a large, easy to read integral LCD display, tri-color bar graph for visual notification of alarm status, programmable low and high alarm relays, and fault relay. Pump flow is self-tuning for maintenance-free operation. Because all GD-70D base units are identical, sensors can be interchanged with no programming or tools required, resulting in maximum flexibility to the user.
  • Monitor combustibles, O2, and a wide range of toxics
  • Monitor vaporized hydrogen peroxide (VHP) fumigation and disinfection
  • Plug and play smart sensors retain calibration and sensor data
  • Common platform (Main unit / Sensor / Pump) for all detection methods
  • Universal main unit (all sensor types)
  • Multifunctional sensor unit (New Intelligent sensor)
  • No internal tubing (main unit) / No coil (pump)
  • Front access, no tool required, easy sensor and pump replacement
  • Large size LCD screen
  • Various communication methods available (4-20mA, NT and PoE)
  • Minimal maintenance cost through enhanced troubleshooting firmware functions
  • Small mounting space
  • Environmentally friendly
  • Wide variety of sensors available
ESU Gas DetectedDetection RangeAlarm 1Alarm 2IncrementsPart #
NH3 (Ammonia)0 - 75.0 ppm25.0 ppm50.0 ppm0.5 ppmGD-70D-NH3
AsH3 (Arsine)0 - 0.20 ppm0.05 ppm0.10 ppm0.001 ppmGD-70D4A-ASH3
BCl3 (Boron trichloride)0 - 15.0 ppm5.00 ppm10.0 ppm0.1 ppmGD-70D-BCl3
Br2 (Bromine)0 - 1.00 ppm0.30 ppm0.60 ppm0.01 ppmGD-70D-BR2
CO (Carbon monoxide)0 - 75.0 ppm 25.0 ppm50.0 ppm0.5 ppmGD-70D-CO-02
0 - 75.0 ppm25.0 ppm50.0 ppm0.5 ppmGD-70D-CO-12
0 - 150 ppm50.0 ppm100 ppm1 ppmGD-70D-CO-01
0 - 150 ppm50.0 ppm100 ppm1 ppmGD-70D-CO-11
0 - 300 ppm100 ppm200 ppm2 ppmGD-70D-CO-03
0 - 300 ppm100 ppm200 ppm2 ppmGD-70D-CO-13
Cl2 (Chlorine)0 - 3.00 ppm1.00 ppm2.00 ppm0.02 ppmGD-70D-Cl2
ClF3 (Chlorine trifluoride)0 - 0.60 ppm0.20 ppm0.40 ppm0.005 ppmGD-70D-ClF3-A
B2H6 (Diborane)0 - 0.30 ppm0.10 ppm0.20 ppm0.002 ppmGD-70D-B2H6
H2Cl2Si (Dichlorosilane)0 - 15.0 ppm5.00 ppm10.0 ppm0.1 ppmGD-70D-DCS
Si2H6 (Disilane)0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-Si2H6
DMA (Dimethylamine)0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-DMA
DEA (Diethylamine)0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-DEA
F2 (Fluorine)0 - 3.00 ppm1.00 ppm2.00 ppm0.02 ppmGD-70D-F2
GeH4 (Germane)0 - 0.80 ppm0.20 ppm0.40 ppm0.005 ppmGD-70D-GeH4
HBR (Hydrogen bromide)0 - 6.00 ppm2.00 ppm4.00 ppm0.05 ppmGD-70D-HBR-06
0 - 9.00 ppm3.00 ppm6.00 ppm0.05 ppmGD-70D-HBR-09
HCl (Hydrogen chloride)0 - 6.00 ppm2.00 ppm4.00 ppm0.05 ppmGD-70D-HCL-06E
0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-HCL-15E
HCN (Hydrogen cyanide)0.9 - 15.0 ppm4.0 ppm10.0 ppm0.1 ppmGD-70D-HCN
HF (Hydrogen fluoride)0.4 - 3.00 ppm1.00 ppm2.00 ppm0.02 ppmGD-70D-HF-03
0.4 - 9.00 ppm3.00 ppm6.00 ppm0.05 ppmGD-70D-HF-09
H2O2 (Hydrogen peroxide)0 - 3.00 ppm1.00 ppm2.00 ppm0.02 ppmGD-70D-H2O2
H2Se (Hydrogen selenide)0 - 0.20 ppm0.05 ppm0.10 ppm0.001 ppmGD-70D-H2Se
H2S (Hydrogen sulfide)0 - 1.00 ppm0.30 ppm0.60 ppm0.01 ppmGD-70D-H2S-01
0 - 30.0 ppm10.0 ppm20.0 ppm0.2 ppmGD-70D-H2S-30
CH3NH2 (Methylamine)0 - 15.0 ppm5.00 ppm10.0 ppm0.1 ppmGD-70D-CH3NH2
NO (Nitric oxide)0 - 100 ppm5 ppm10 ppm1 ppmGD-70D-NO
NO2 (Nitrogen dioxide)0 - 9.00 ppm3.00 ppm6.00 ppm0.05 ppmGD-70D-NO2-09
0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-NO2-15
N2O4 (Nitrogen Tetraoxide)0 - 15.0 ppmGD-70D-N2O4
NF3 (Nitrogen trifluoride)0 - 30.0 ppm10.0 ppm20.0 ppm0.2 ppmGD-70DP-NF3
O3 (Ozone)0 - 0.60 ppm0.20 ppm0.40 ppm0.005 ppmGD-70D-O3
PH3 (Phosphine)0 - 1.00 ppm0.30 ppm0.60 ppm0.01 ppmGD-70D-PH3-AH
0 - 1.00 ppm0.30 ppm0.60 ppm0.01 ppmGD-70D-PH3-DH
SiH4 (Silane)0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-SiH4-AH
0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-SiH4-DH
SiCl4 (Silicon tetrachloride)0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-SiCl4
SO2 (Sulfur dioxide)0 - 6.00 ppm2.00 ppm4.00 ppm0.05 ppmGD-70D-SO2
TEOS (Tetraethyl
orthosilicate)
0 - 15.0 ppm10.0 ppm10.0 ppm0.1 ppmGD-70DP-TEOS
TMA (Trimethylamine)0 - 15.0 ppm5.0 ppm10.0 ppm0.1 ppmGD-70D-TMA
Model GD-70D GD-70D-NT GD-70D-ET
Communication 4-20mA DC DC power line communication PoE Method
Detection principle Different type depending upon sensor unit and detectable gas (see table)
Sampling method Sample drawing types (auto-adjustment of flow rate) 0.5 / min +/-10%
Display
  • Large LCD display (white backlight)
  • Gas concentration
  • Flow rate, communication status, Pyrolyzer status, gas detected
  • Error code, content of error
Gas alarms Two alarm levels: 1st alarm – Red 2nd alarm – Red Fault alarm: Yellow
External output 1st, 2nd, and trouble alarms : Relay contact output for each alarm
Self diagnostic function System failure, sensor failure, flow failure, communication error NT / ET / Analog
Datalogging Event history, alarm history, calibration history. Alarm trend (180 sec before / after 1st alarm)
Operation temp. & humidity 0 ~ 40ºC, 30 ~ 70% RH (non-condensing)
Operating settings All operational settings are user adjustable through front panel
Power requirements DC 24V+/- 10%, approx 1.5W (Max 4W including sensor unit) Note: Approx. 2.5W (Max 5W) with SGU sensor unit PoE standard arrangement
Dimensions 2.8”W x 4.7”H x 5.9”D (70W x 120H x 150Dmm)
Weight Approx. 0.9kg (2.0lbs), including sensor unit
Mounting Wall-mounting base plate by 2 or 3 screws
Sampling tubing 4 x 6mm PTFE tubing recommended. Tube fittings provided as standard accessories
Bushing Cable type varies depending on communication method (Cable bushing optional)

SENSOR UNIT

Model ESU SGU SSU NCU
Detection Principle Electro-chemical cell Semi-conductor Pyrolysis-particle Catalytic combustion
Gas detected and detection range Refer to list of detectable gases 0-2000ppm H2, CH4, or CH2F2 (R-32) in air and others 0-15ppm TEOS in air 0-100% LEL H2, CH4, and others
Self diagnosis function Sensor trouble, system failure
Date logging function Event history, alarm history, calibration history, Alarm trend (60 sec. before/after 1st alarm)

PYROLYSER UNIT

Model PLU-70
Application NF3 / TEOS gases detected in air
Usage Used by connecting to “GD-70D” (Main unit)
Power Lamp
  • LED (Green color)
  • Normal: Light-on
  • Warming-up: Flashing at every 1 sec interval
  • Trouble: Flashing at every 0.2 sec interval
Self-diagnostic function
  • Pyrolyser unit trouble
  • Fan trouble
  • System trouble
Operating temp. & humidity 0-40° C, 30-70% RH (non-condensing)
Operational settings All operational settings are user adjustable through front panel.
Power requirements DC 24V+/- 10%, approx. 25W (max)
Dimensions 2.8”W x 4.7”H x 5.9”D (70W x 120H x 150Dmm)
Weight Approx. 1.2kg (2.6lbs)
Mounting Wall-mounting base plate by 2 or 3 screws
Sampling 4x6mm PTFE tubing recommended. Tube fittings provided as standard accessories
Bushing 1.25sq 2 core cable for power supply DC24V (Cable bushing optional)

Additional information

Weight 2 lbs
Dimensions 5.9 × 2.8 × 4.7 in